Cable Termination Kits

    Type
    : Cable Terminal and Joint
    Material
    : High elasticity silicon rubber
    Surface Treatment
    : Insulative
    Applicable voltage
    : 1kv 11kv 33kv
    Special
    : Shrink Power Cable Straight
    Name
    : Cold / Hot Shrink Terminal
    Cores : 1-Core, 2-Core, 3-Core, 4-Core, 5-Core
    Usage
    : Connecting Cable
    Application
    : Indoor / Outdoor
    Place of Origin
    : P. R. China
    Color : Red Blue Black Yellow
  • Description
  • Technical Data
  • Mounting & Dimension
  • Production Standards
  • Inquiry

1KV.11KV. 33KV SERIES COLD-SHRINKABLE CABLE ACCESSORIES (TERMINATION KIT)



Cable Termination Kit Characteristic

Injecting shaping the lipuid silicon rubber, having shrink pressure for the cable conductor, respire with cable together, low parlial discharging. Using water-proof insulating tape recover the inner and outer protecting shed, sealed well. Using special armour for outer protecing, installed conveniently. Suitable for 6-35kv silicon rubber insulating cable interconnecting, can be used in mine shaft or underwater, etc bad surroundings.

Convenient Installation

Shrink technique, no need to use fire or special tool, no need to joint or bind copper wire, spring earthing. It can save labour force, time and space, every set of products are packed with installation introduction.

Broad Application

The cold shrink termination is made by special pre-expand technology, even one  kind of specification can fit for many kinds of cable wire dimension with good compatibility. For the structure it is prefab compact designed, making a  complete line of stress control tube, rain shed and insulation tube. up to now, we have possessed complete series of 33KV (others less than 35KV) the cold shrink termination fit for different variety of insulated cables such as polythene cable and XLPE polythene cable, etc. Applicable for bridge stand, embedding and trollywire and so on. The silasticma-terials indicate large use range for the cold shrink termination.

Specification
Item Description of goods Specification Applicable Section (mm2)
10KV one core Indoor termination kit HS-NLS-10/1X1 25-50
HS-NLS-10/1X2 70-120
HS-NLS-10/1X3 150-240
HS-NLS-10/1X4 300-400
Outdoor termination kit HS-WLS-10/1X1 25-50
HS-WLS-10/1X2 70-120
HS-WLS-10/1X3 150-240
HS-WLS-10/1X4 300-400
Straight through joint HS-JLS-10/1X1 25-50
HS-JLS-10/1X2 70-120
HS-JLS-10/1X3 150-240
HS-JLS-10/1X4 300-400
20KV Three core Indoor termination kit HS-NLS-10/3X1 25-50
HS-NLS-10/3X2 70-120
HS-NLS-10/3X3 150-240
HS-NLS-10/3X4 300-400
Outdoor termination kit HS-WLS-10/3X1 25-50
HS-WLS-10/3X2 70-120
HS-WLS-10/3X3 150-240
HS-WLS-10/3X4 300-400
Straight through joint HS-JLS-10/3X1 25-50
HS-JLS-10/3X2 70-120
HS-JLS-10/3X3 150-240
HS-JLS-10/3X4 300-400


Testing
No. Test Project Standard Requirements Conclusion
1 AC withstand voltage test 39KV 5min No Flashover and No Breakdown Qualified
2 AC withstand voltage test under rain 35KV 1min No Flashover and No Breakdown Qualified
3 Partial discharge test at ambient temperature The magnitude of the discharge at 15 kV shall not exceed 10 pC Qualified
4 Impulse withstand voltage test at 95¡«100¡ãC ¡À10 impulses of 95kV No flashover and No Breakdown
5 Heating cycle voltage test in air 60 cycles in air at the conductor tempreture of 95¡«100¡ãC and 22kV No flashover and be assessed by the following test result
6 Partial Discharge test at 95¡æ¡«100¡æ at ambient temperature Under 15KV, Discharge volume¡Ü10pc Qualified


Specification
Item Description of goods Specification Applicable Section (mm2)
10KV one core Indoor termination kit HS-NLS-10/1X1 25-50
HS-NLS-10/1X2 70-120
HS-NLS-10/1X3 150-240
HS-NLS-10/1X4 300-400
Outdoor termination kit HS-WLS-10/1X1 25-50
HS-WLS-10/1X2 70-120
HS-WLS-10/1X3 150-240
HS-WLS-10/1X4 300-400
Straight through joint HS-JLS-10/1X1 25-50
HS-JLS-10/1X2 70-120
HS-JLS-10/1X3 150-240
HS-JLS-10/1X4 300-400
20KV Three core Indoor termination kit HS-NLS-10/3X1 25-50
HS-NLS-10/3X2 70-120
HS-NLS-10/3X3 150-240
HS-NLS-10/3X4 300-400
Outdoor termination kit HS-WLS-10/3X1 25-50
HS-WLS-10/3X2 70-120
HS-WLS-10/3X3 150-240
HS-WLS-10/3X4 300-400
Straight through joint HS-JLS-10/3X1 25-50
HS-JLS-10/3X2 70-120
HS-JLS-10/3X3 150-240
HS-JLS-10/3X4 300-400


Test Data
No. Test Project Standard Requirements Conclusion
1 AC withstand voltage test 39KV 5min No Flashover and No Breakdown Qualified
2 AC withstand voltage test under rain 35KV 1min No Flashover and No Breakdown Qualified
3 Partial discharge test at ambient temperature The magnitude of the discharge at 15 kV shall not exceed 10 pC Qualified
4 Impulse withstand voltage test at 95¡«100¡ãC ¡À10 impulses of 95kV No flashover and No Breakdown
5 Heating cycle voltage test in air 60 cycles in air at the conductor tempreture of 95¡«100¡ãC and 22kV No flashover and be assessed by the following test result
6 Partial Discharge test at 95¡æ¡«100¡æ at ambient temperature Under 15KV, Discharge volume¡Ü10pc Qualified